Monografia

Análise do potencial da tensão de sequência positiva para detectar e distinguir o rompimento do condutor em sistemas de distribuição de energia elétrica

The rupture of energized conductors in the distribution system, when in contact with a high impedance surface, such as the soil, represents a great risk to human life, and can even cause major fires. Conventional overcurrent protection equipment has a great limitation for detecting this type o...

ver descrição completa

Autor principal: Santos, Natalia Ferreira Teles dos
Grau: Monografia
Idioma: pt_BR
Publicado em: Universidade Federal do Tocantins 2021
Assuntos:
ATP
Acesso em linha: http://hdl.handle.net/11612/2912
Resumo:
The rupture of energized conductors in the distribution system, when in contact with a high impedance surface, such as the soil, represents a great risk to human life, and can even cause major fires. Conventional overcurrent protection equipment has a great limitation for detecting this type of fault, and despite the progress in the study of the problem and the probability of detecting these faults, these methods still do not have high reliability and safety in terms of detection. In addition, in these methods, there is no way to locate the fault by the protection system alone. However, some recent studies propose a detection of the rupture of conductors due to voltage imbalance. Then, this work offers a method of detecting conductor breakage and distinguishing from other disturbances, using the positive sequence voltage as a monitoring parameter. Simulations were performed in the Alternative Transients Program, using the IEEE 34 bus system as a test system. These simulations involved the modeling of the distribution system itself as well as the disorders studied here which are: sag, swell, as well as the switching of capacitor banks, switching of concentrated loads, switching of distributed loads, switching of side branches, switching of loads non-linear and conductor disruption that can cause disturbances in the electrical system. Subsequently, by means of mathematical software, analyzes were carried out in order to locate and distinguish the disturbances of the driver's disruption. After analyzing the results, the method presented satisfactory results, and can be a useful tool for the operator of the electrical system.